Local Pressure Factor (Kl) Calculator

AS/NZS 1170.2:2011 — Table 5.6 | Guided roof and wall zone selection

1. What are you designing?

Main structural system — global wind actions: Use Kl = 1.0. No local pressure-zone selection is needed for this design purpose. If the member also directly supports cladding, perform a separate local component/connection check.

2. Building geometry and loaded area

Use the distance and edge definition indicated for the selected zone in Figure 5.3. Verify the loaded-area extent.
Enter r using the Standard's definition for the wind direction; do not assume r = b/d without checking.
For upwind roof-edge checks, enter the distance to the second roof edge as well. RC1 can govern when the loaded area is near both edges. The example uses a = min(0.2b, 0.2d, h), consistent with the earlier worked example. Verify the exact definition and any minimum limits in your copy of Figure 5.3 before design use. You can switch to a manually verified a. For zone checks, the calculator uses the conditions in the Table 5.6 image you provided.

3. Factor to use for the selected element

Main structure — global wind analysis
Kl = 1.0

Use this value for overall wind analysis of core walls, columns, primary beams and main portal frame rafters. This is not a cladding or direct cladding-support check.

Separate check: If a member or connection directly carries local cladding loads, select the local component/connection option above and assess its relevant load path.

ZoneTable 5.6 requirementsChecksKlApplicable?

4. Understanding the result

RA1 versus RA2: RA1 permits A ≤ a² and distance < a, giving Kl = 1.5. RA2 is a smaller loaded-area case, A ≤ 0.25a², closer to the edge (< 0.5a), giving Kl = 2.0. Both may apply; select the larger applicable factor.

For side walls: the aspect ratio r changes which SA zones apply. The calculator checks the appropriate SA group, including SA3 beyond a for r > 1.

For a main rafter: the global frame analysis uses Kl = 1.0 for this purpose. Check separate local purlin reactions, cladding-support connections or directly supported cladding where relevant.

Engineering limitations: This tool implements the numerical thresholds in the Table 5.6 screenshot for local cladding checks. The roof-edge case also checks RC1, using both entered edge distances. The table does not by itself establish which geometric zone a particular component occupies: confirm the correct zone, direction, roof type, distances, loaded-area extent, r definition and Figure 5.3 notes. Roof corner RC1 and roof-edge zones may overlap. Do not apply the factors to positive-pressure cases other than WA1. Other wind factors and load combinations must be checked separately.
Local Pressure Factor (Kl) Calculator

User Guide | AS/NZS 1170.2:2011 — Wind Actions | Clause 5.4.4, Table 5.6 and Figure 5.3

1. Introduction

The Local Pressure Factor (Kl) Calculator assists structural engineers and designers in determining local wind pressure factors for buildings in accordance with AS/NZS 1170.2:2011, particularly Clause 5.4.4, Table 5.6 and Figure 5.3.

Local pressure factors account for increased wind pressures or suctions that can occur in particular regions of a building, especially near roof edges, roof corners, ridges and wall edges. These local effects can be higher than pressures used for overall structural analysis.

The calculator guides users through building-zone selection, loaded-area and distance checks, and identification of the applicable local pressure factor.

2. When should Kl be used?

Main structural elements — global wind analysis

For the overall wind analysis of the primary structural system, the local pressure factor is generally:

Kl = 1.0

Examples include core walls, shear walls, main columns, primary beams and rafters, portal frames and principal lateral load-resisting systems.

Cladding and immediate cladding supports — local wind analysis

The local factors in Table 5.6 may apply to roof sheeting, wall cladding, façade panels, purlins, girts, cladding fixings and connections, and other elements directly supporting cladding.

Important distinction: A main rafter may use global wind actions for overall frame analysis but still require a separate local check where a purlin transfers a concentrated uplift reaction into the rafter or its connection.

3. How to use the calculator

1Select the design element

Choose the element or design purpose. Main structure/global analysis generally returns Kl = 1.0. For cladding and immediate supports, select the relevant local design case.

2Enter building geometry

Enter building width b (m), depth d (m) and height h (m). Confirm the reference dimension and definitions against the Standard.

3Identify the relevant zone

Use the wind direction, roof pitch, building proportions and element location to select the applicable roof or wall zone from Table 5.6 and Figure 5.3.

4Enter loaded area and distance

Enter the effective loaded area A (m²) and the distance from the relevant edge. For example, a 5 m purlin span with 1.5 m tributary width gives A = 7.5 m².

5Check Table 5.6 conditions

Review the applicable area, edge-distance, roof-pitch and aspect-ratio requirements. A zone applies only when all its relevant conditions are met.

6Review the result

The calculator displays the selected local pressure factor and governing zone. Check all potentially overlapping zones before adopting the result for design.

Table 5.6 zone guide

ZoneGeneral description
WA1Positive local pressure on windward walls
RC1Negative local pressure at qualifying roof corners
RA1–RA2Negative local pressure near upwind roof edges
RA3–RA4Negative local pressure on the downwind side of qualifying hips and ridges
SA1–SA5Negative local pressure regions on sidewalls, depending on aspect ratio and location
Geometry note: WA1 is on the windward wall. SA zones are on sidewalls, not the same wall face. RA3 and RA4 should not be treated as generic “inner roof” zones.

4. Worked example — roof purlin

Consider a warehouse with the following illustrative dimensions and purlin tributary area:

ParameterValue
Building width, b30 m
Building depth, d40 m
Building height, h10 m
Purlin span5 m
Tributary width1.5 m
Loaded area, A7.5 m²
Distance from upwind roof edge2 m

For the illustrative reference dimension a = 6 m:

A = 5 × 1.5 = 7.5 m²
CheckRA1RA2
Loaded-area limitA ≤ 36 m²A ≤ 9 m²
Distance limit< 6 m< 3 m
Example satisfies both?YesYes
Local pressure factor1.52.0
Kl = 2.0   (RA2 governs)

This example assumes the RA2 roof-edge case applies and that no other applicable local zone, such as a qualifying roof corner, governs the same loaded area.

5. Important engineering considerations

  • Do not apply a local pressure factor automatically to the entire building or the complete roof.
  • Distinguish global structural response from local cladding and support-member effects.
  • Check concentrated local reactions transmitted into primary members and connections.
  • Use the correct loaded-area definition and measure distances from the relevant edges as specified in the Standard.
  • Confirm that the relevant wind direction, roof pitch, zone geometry and all Table 5.6 notes are satisfied.

6. Standard reference and limitations

Reference: AS/NZS 1170.2:2011 — Structural Design Actions, Part 2: Wind Actions; Clause 5.4.4, Table 5.6 and Figure 5.3.

This calculator is an educational and engineering design aid, not a substitute for a complete wind-loading assessment or professional engineering judgement. Independently verify zone boundaries, reference dimensions, loaded areas and applicability before using results for structural design, certification or construction.

Edition notice: This guide relates to the 2011 edition of AS/NZS 1170.2. If your project is governed by another edition, confirm the corresponding provisions and use a calculator developed for that edition.