Calculation of Action Combination Factor (Kc,e) and Area Reduction Factor (Ka)
AS/NZS 1170.2:2011 • Clause 5.4.2 • Table 5.4 • External wind pressure
1. Select the surface and design area
Clause 5.4.2: Table 5.4 applies to roofs and sidewalls; other cases use Kₐ = 1.0.
Tributary area is the area contributing to the force/action being considered.
Use the effective tributary area of the member or component being designed, not necessarily the total building area.
Clause 5.4.2: A is the area contributing to the force being considered. For a beam, this may be its tributary width multiplied by the relevant span or length. For a cladding panel, it may be the supported panel area. The chosen area must be appropriate to the structural action being checked.
2. Area reduction coefficient — Table 5.4
Tributary area A (m²)Area reduction factor KₐInterpretation
A ≤ 101.00No area reduction
A = 250.90Tabulated intermediate point
A ≥ 1000.80Minimum Table 5.4 coefficient
Table 5.4 Note: use linear interpolation between tabulated areas. Values are bounded between 0.80 and 1.00 for the applicable roof and sidewall cases; do not extrapolate beyond the table.
3. Live calculation and interpolation
Tributary area A—m²
Applicable surface—Clause 5.4.2
Reduction—Relative to Kₐ = 1.0
Calculated area reduction factor
Kₐ = —
4. Graph — Kₐ versus tributary area
1.000.900.8001025100Tributary area A (m²)KₐSelected A
Blue line: Table 5.4 for roof and sidewall cases. Orange marker: selected area. For W, L and other surfaces the final Kₐ is 1.0 regardless of this reference curve.
Reference: AS/NZS 1170.2:2011, Clause 5.4.2 and Table 5.4. This calculator determines only the external area reduction factor Kₐ.
5. Action combination factor — Kc,e
Select the combination relevant to the structural action, not merely the number of surfaces on the building. Confirm applicability against AS/NZS 1170.2:2011 Clause 5.4.3 and Table 5.5.
Use only when justified by the relevant standard provision. Leave blank for the selection above.
Contributing surfaces (simplified selection)Kc,e
One1.00
Two0.90
Three or more0.80
Combined factor check: For roof and sidewall cases, apply the minimum to the product Kₐ × Kc,e: Kcombined = max(Kₐ × Kc,e, 0.80). For other surfaces, Kₐ = 1.0; the roof/sidewall product floor is not automatically imposed. Check the complete Table 5.5 provisions for your actual load combination.
Area factor—
Selected Kc,e—
Unadjusted product—
Final combined factor Kₐ × Kc,e (after applicable minimum)
—